Installation must comply with the technical standards applicable in each territory Code of
practice for design and fixing of roofs with clay roofing tiles and Tejas Borja specifications.
FITTING
Roof tiles on the roof surface must be fixed to the support to a greater or lesser extent, depending on the pitch. In the case of
singular points such as eave lines, edges, hip lines, valleys, joints and the ridge line, all roof tiles and accessories of these joints
must be fixed to the battens.
We recommend that all roof tiles that form the perimeter of each skirt be fixed mechanically.
Metallic
Batten type:
Treated wood
3%
17
Dry installation:
Self-drilling stainless screws or nails - %
(depending on the support)
0o 00
6- 1
C
45o
B
A25%-100% The roof tiles will rest on battens, since they are provided with
nib support.
A
B 100%-173%
All the roof tiles around the perimeter of each roof surface %
must be fixed and at least one in every five should be fixed in
14o - 25
a regular manner.
C > 173%
In areas with strong winds, exposed areas or areas with basic
seismic acceleration of > 0.12g, all roof tiles should be fixed 0o - 0%
mechanically to the battens.
Less than 25% - Not recommended
Fitting system LEVEL B
ROWS
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
6
5
4
UN
3
P
2
S
1
0
VENTILATION
Under-tile ventilation is necessary at all times. This will
guarantee the durability of the material used to build
the roof with their optimal characteristics, improving the
hygrothermal performance of the roof tiles against the ROWS
moisture resulting from condensation.
1
2
3
4
5
6
7
8
9
There must be a continuous air flow between eave lines 7
and ridge line. To this end, a space must be left between 6
the roof tiles and the support. As a result, eave lines,
ridge lines and singular points must never be filled in with 5
N
4
U
mortar, as this will impede micro-ventilation.
P
3
S
Ventilation roof tiles will also be installed in a uniform
manner across the surface of the roof. In case of dry 2
installation, it is recommended that at least 1 ventilation
1
roof tile be used every 10 sq.m. and 4 ventilation roof
tiles per the roof surface.
Example case of distribution of ventilation roof tiles
on a 7m x 9m rectangular roof surface (63 sq.m.)
49