Installation must comply with the technical standards applicable in each territory Code of 
practice for design and fixing of roofs with clay roofing tiles and Tejas Borja specifications.




 

FITTING


 
Roof tiles on the roof surface must be fixed to the support to a greater or lesser extent, depending on the pitch. In the case of 

singular points such as eave lines, edges, hip lines, valleys, joints and the ridge line, all roof tiles and accessories of these joints 
must be fixed to the battens.


We recommend that all roof tiles that form the perimeter of each skirt be fixed mechanically.



  Metallic
  
Batten type:

    Treated wood
3%

  17
Dry installation:
 Self-drilling stainless screws or nails - %

(depending on the support)
0o 00
6- 1
 C
45o 

B

A25%-100% The roof tiles will rest on battens, since they are provided with 
nib support.

A 
B 100%-173%
All the roof tiles around the perimeter of each roof surface %

must be fixed and at least one in every five should be fixed in
14o - 25
a regular manner.


C > 173%
In areas with strong winds, exposed areas or areas with basic 
seismic acceleration of > 0.12g, all roof tiles should be fixed 0o - 0%

mechanically to the battens.

Less than 25% - Not recommended




 Fitting system LEVEL B


ROWS

                                           
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20

6
                        

5
                        
                        
4

                        UN

3
P
2
                        S

1
                        
                        
0

                        



VENTILATION


 


Under-tile ventilation is necessary at all times. This will 
guarantee the durability of the material used to build 

the roof with their optimal characteristics, improving the 
hygrothermal performance of the roof tiles against the ROWS

moisture resulting from condensation.
                    1
2
3
4
5
6
7
8
9


There must be a continuous air flow between eave lines              7

          
and ridge line. To this end, a space must be left between            6

the roof tiles and the support. As a result, eave lines,              
ridge lines and singular points must never be filled in with 5
N

                   4
U
mortar, as this will impede micro-ventilation.
P
                     3
S
Ventilation roof tiles will also be installed in a uniform              
manner across the surface of the roof. In case of dry 2

installation, it is recommended that at least 1 ventilation              
1

roof tile be used every 10 sq.m. and 4 ventilation roof           
tiles per the roof surface.
Example case of distribution of ventilation roof tiles 
on a 7m x 9m rectangular roof surface (63 sq.m.)






49


   49   50   51   52   53